Click 100–400 SeriesUSER GUIDE
Part IIntroduction to the Click SeriesChapter 1 – The Power PlantChapter 2 – T-bus BasicsChapter 3 – Wiring the DevicesChapter 4 – Installing Click Su
CHAPTER 9 CLICK 110 99not all combinations of enabled and disabled channels are listed. A complete table is shown below.Level 1 LEDs Cha
100 CHAPTER 9 CLICK 110Because this parameter can also be set by the DIP switches, you may need to ensure that the DIP switches are set to Sowar
CHAPTER 9 CLICK 110 101Aer you have viewed the outstation mode conguration, press and release the mode switch to exit.Reset to Default Settin
102 CHAPTER 9 CLICK 110NoteSome of the parameters mentioned below can only be configured in Click Supervi-sor. Others can be configured by the fron
CHAPTER 9 CLICK 110 103Figure 9.10 – Expert Driver General TabNoteThis parameter can only be configured using Click Supervisor.Setting Descripti
104 CHAPTER 9 CLICK 110e System > Settings tab lets you congure and view many of the parameters that are also available elsewhere on the dev
CHAPTER 9 CLICK 110 105Outstation ModeLets you view which brand of outstation, Peek or Siemens, the device is currently set to work with. See O
106 CHAPTER 9 CLICK 110NoteIf you do not save your settings to your Click 110, they will be lost the next time you power the device down. e To
In this chapter Physical Features Installation and Wiring Configuration DIP Switches Front Panel Menu Click Supervisor10e Click 112 and 11
108 CHAPTER 10 CLICK 112/114Physical Featurese following sections describe the physical features of the Click 112/114.Figure 10.2 – Diagram of t
CHAPTER 10 CLICK 112/114 109LEDse faceplate of the Click 112/114 has three banks of LEDs. e top bank is used for detec-tion indication, the s
110 CHAPTER 10 CLICK 112/114112/114 devices (covered in the DIP Switches section of this chapter).2 Insert the cards into the slots on the detec
CHAPTER 10 CLICK 112/114 111NoteFor specific information on how to use the Click 112/114 with the SmartSensor Matrix, see the SmartSensor Matrix
112 CHAPTER 10 CLICK 112/114One benet of using DIP switches to congure is that if you ever have a eld service call and need to replace a Click
CHAPTER 10 CLICK 112/114 113 Bus 2 baud rate Channel input mapFor each parameter, if any individual switch is in the ON position, that para
114 CHAPTER 10 CLICK 112/114S4: Input Mapping1 2 3 4 ChannelO O O O Software modeO O O On 1–2O O On O 3–4O O On On 5–6O On O O 7–8
CHAPTER 10 CLICK 112/114 115Baud Ratee baud rates for the two RS-485 buses, bus 1 and bus 2 (see the faceplate of the device for which RJ-11 j
116 CHAPTER 10 CLICK 112/114conguring the menu options. Level 2 LEDs only light up when a menu selection is made using the Level 1 LEDs.
CHAPTER 10 CLICK 112/114 117e following table illustrates an example of how the mode switch and menu indicator LEDs are used in conguring the
118 CHAPTER 10 CLICK 112/114Figure 10.6 – Front Panel Menu LabelAs shown above, the menu options are displayed on the Level 1 LEDs (multicolored)
In this chapter Connecting to a Circuit Breaker Connecting AC Surge Protection Connecting Power1Power and surge protection are provided to your
CHAPTER 10 CLICK 112/114 119As mentioned earlier, the Click 112/114 devices receive serial datagrams from a SmartSen-sor. ese datagrams can co
120 CHAPTER 10 CLICK 112/114Level 1 LEDs Input MappingLevel 2 LEDs Cancel and exit menu Channels 1–4 Channels 5–8
CHAPTER 10 CLICK 112/114 121Level 1 LEDs AutobaudLevel 2 LEDs Cancel and exit menu Autobaud on bus 1 LED o LED on
122 CHAPTER 10 CLICK 112/114Level 1 LEDs Baud rate for bus 1 Baud rate for bus 2Level 2 LEDs Cancel and exit menu 960
CHAPTER 10 CLICK 112/114 123Aer the Click 112/114 has reset to factory defaults, it will check the DIP switches; if any of them are set to Har
124 CHAPTER 10 CLICK 112/114e Backups option can be used to read congurations that have previously been saved to le. See Chapter 5 for more in
CHAPTER 10 CLICK 112/114 125Firmware VersionShows the version of firmware your device currently has installed. If Click Supervisor detects a dis
126 CHAPTER 10 CLICK 112/114Input MappingLets you assign input datagram channels received from the sensor to the two or four output channels on t
CHAPTER 10 CLICK 112/114 127NoteIf you do not save your settings to your Click 112/114, they will be lost the next time you power the device do
12 CHAPTER 1 THE POWER PLANTNoteThe power plant will only be used if your cabinet is supplied with AC power. If DC is coming into your cabinet, y
In this chapter Physical Features Installation11e Click 120/121 provide an interface between Click contact closure devices and signaling systems.
130 CHAPTER 11 CLICK 120/121Physical FeaturesFigure 11.2 – Diagram of the Click 120e Click 120/121 feature ve terminals. On the Click 120, thes
CHAPTER 11 CLICK 120/121 131devices. To remove a Click 120/121 from the DIN rail, insert a small screwdriver into the notch at the upper back c
132 CHAPTER 11 CLICK 120/1213 Wire from the A2– terminal on the coil side of each relay to the correct output termi-nals on the contact closure
In this chapter Physical Features Installing and Wiring the Click 172/174 Operation Modes Power and Configuration Verify Operation Fail-sa
134 CHAPTER 12 CLICK 172/174Physical Featurese following sections describe the features of the Click 172/174 cards (see Figure 12.2):Figure 12.2
CHAPTER 12 CLICK 172/174 135 Low Power (LP)NoteThe first number in the lane name is the number specified in SmartSensor Manager. If no number i
136 CHAPTER 12 CLICK 172/174and then assigned to the correct trac phases.Installing and Wiring the Click 172/174Use the following steps to insta
CHAPTER 12 CLICK 172/174 1371L (One Loop Speed)Outputs contact closures for single-loop emulation. The duration of each contact closure output
138 CHAPTER 12 CLICK 172/174In order to mimic a traditional system, the rack card’s processor will sequence activation of the primary and seconda
CHAPTER 1 THE POWER PLANT 13Figure 1.2 – Click 230 Screw Terminals (labels beneath terminals have been added)Screw terminals 3 and 4 are direct
CHAPTER 12 CLICK 172/174 139Power and Configuratione Click 172/174 will automatically power up when the cards are inserted into a detector card
140 CHAPTER 12 CLICK 172/174NoteIf several Click 172/174 cards are daisy-chained, configure each card separately to en-sure that only one device i
CHAPTER 12 CLICK 172/174 141NoteIf outputs 1 and 2 on the Click 174 have been configured to the same lane, then out-puts 3 and 4 cannot be config
142 CHAPTER 12 CLICK 172/174e Click 172/174 cards are also able to display counts and speeds of the vehicles in the lanes being monitored for ve
CHAPTER 12 CLICK 172/174 143NoteYou do not want to connect to the DB-9 on the Click 200 because this will connect you to the sensor’s native RS
In this chapter Physical Features Installation13e Click 200 module is designed to protect SmartSensors from surges on all power and communication
146 CHAPTER 13 CLICK 200Physical Featurese physical features of the Click 200 include communication and power connections.Figure 13.2 – The Clic
CHAPTER 13 CLICK 200 147NoteThe Click 200 does not convert RS-232 to RS-485 or vice versa. Connecting to the DB-9 connector will allow you to c
148 CHAPTER 13 CLICK 200Follow the steps below to include surge protection using Click 200 devices (see Figure 13.3):1 Install a Click 200 devic
14 CHAPTER 1 THE POWER PLANTWiring AC Power into the Click 201/202/204Use the steps below to properly wire AC power to the top of the Click 201/2
CHAPTER 13 CLICK 200 149If you have a 9-conductor cable, there is a ground (gray) wire and a total of three drains; these can all be wired into
150 CHAPTER 13 CLICK 200Figure 13.5 – Verifying Earth Ground3 e resistance should measure less than one ohm. If not, the most likely problem is
In this chapter Physical Features Installation14Click 201/202/204 modules are 120–240 VAC to 24 VDC power supplies. One of these modules should be
152 CHAPTER 14 CLICK 201/202/204Physical FeaturesClick 201/202/204 modules have the following physical features.Figure 14.2 – Diagram of the Clic
CHAPTER 14 CLICK 201/202/204 153rectly wire the Click 201/202/204.NoteEnsure power to AC mains is disconnected while wiring the AC input.Wiring
154 CHAPTER 14 CLICK 201/202/204Figure 14.4 – Wiring DC Power out of the Click 201/202/204NoteDo not wire out of the DC OK terminal; it supplies
In this chapter Physical Features Installation On-device Configuration15e Click 203 is a combination uninterrupted power supply and battery, kee
156 CHAPTER 15 CLICK 203NoteBecause the Click 203 is a power supply, if you are using one, you do not need a Click 201/202/204.Physical Features
CHAPTER 15 CLICK 203 157NoteThe battery fuse must be removed when installing or replacing the module.InstallationUse the following tables to wi
158 CHAPTER 15 CLICK 203Remote Shutdowne R1 and R2 screw terminals are used for the remote shutdown function. When remote shutdown is active, th
CHAPTER 1 THE POWER PLANT 15Figure 1.4 – Wiring DC Power out of the Click 201/202/204CautionAn authorized electrical technician should perform
CHAPTER 15 CLICK 203 159Buer mode LED o LED on; battery mode out-put: 24 V, battery charge: 0 VLED o; output: 0 VRechargeable battery disch
In this chapter Physical Features Installation16e Click 210 is a compact circuit breaker DIN rail device designed to interrupt an electric curren
162 CHAPTER 16 CLICK 210NoteThe Click 210 is a 0.5 A circuit breaker. There are also 2 A and 8 A models available; contact your Wavetronix dealer
In this chapter Physical Features Installation17e Click 211 is an AC outlet that provides a standard three-hole socket for devices pow-ered throu
164 CHAPTER 17 CLICK 211NoteWiring the Click 211 from the power plant requires the use of two twin terminal blocks.Physical FeaturesFigure 17.2 –
CHAPTER 17 CLICK 211 165Wiring the Power Plant1 Install the Click 210 and Click 230 as outlined in Chapter 1.2 Attach two ST 2.5 twin termina
166 CHAPTER 17 CLICK 211Figure 17.4 – Wiring into the Power Supply8 Wire power out of the Click 201/202/204 as described in Chapter 1.Wiring the
In this chapter Physical Features Installation18e Click 221 provides surge protection on DC input lines. Use this device in a cabinet with DC inp
168 CHAPTER 18 CLICK 221Physical FeaturesFigure 18.2 – Diagram of the Click 221e bottom of the Click 221 has a screw terminal block with four sc
In this chapter Physical Features Installation19e Click 222 system surge protection device is designed to prevent electrical surges con-ducted al
170 CHAPTER 19 CLICK 222Physical Featurese physical features of the Click 222 include communication and power connections.LED IndicatorsT-BusCon
CHAPTER 19 CLICK 222 171Configuration Featurese front of the Click 222 has four LEDs that indicate device activity and status: PWR (red) ligh
172 CHAPTER 19 CLICK 222e steps below refer to how to install and wire a Click 222. If you are using a SmartSensor Matrix preassembled cabinet,
CHAPTER 19 CLICK 222 1733 If you are using Click 112 cards, use a short patch cord to share bus 1 between cards dedicated to the same sensor,
In this chapter Physical Features Installation20e Click 223 dual-485 surge protector device is designed to prevent electrical surges from damagin
176 CHAPTER 20 CLICK 223Physical FeaturesFigure 20.2 – Diagram of the Click 223e faceplate of the Click 223 has two RJ-11 jacks, which provide t
CHAPTER 20 CLICK 223 177 Two RS-485 connections, each consisting of one -485 and one +485 terminale front of the Click 223 has an LED that l
178 CHAPTER 20 CLICK 223device, wire it, then reinsert it.)3 Wire the middle pluggable screw terminal block: connect the orange wire to the scre
In this chapter Adding a T-bus to the DIN Rail Mounting Click Devices Wiring T-buses2Now that the power plant is complete, the next step in inst
In this chapter Physical Features Installation21e Click 230 provides up to 10 kA (8/20 μS) of surge protection per AC input line.Figure 21.1 – Th
180 CHAPTER 21 CLICK 230NoteThe Click 230 is designed for use with 120 VAC. A 220 VAC version is available for installations using that voltage.
CHAPTER 21 CLICK 230 1812 Connect the white (neutral) and green (ground) wires from the terminal block or from the AC cord into screw terminal
In this chapter Physical Features Installation22e Click 250 is a 100 MHz–3 GHz bulkhead N-Female to N-Female 90 V coaxial wireless surge protecto
184 CHAPTER 22 CLICK 250Physical FeaturesFigure 22.2 – Diagram of the Click 250e Click 250 is a bulkhead N-Female to N-Female connector; both co
CHAPTER 22 CLICK 250 185Figure 22.4 – Connecting the Grounding Wire2 Get a coaxial cable that’s female on one end and male on the other. Conne
In this chapter Physical Features On-device Configuration Computer Configuration23e Click 301 serial to Ethernet converter changes half-duplex tw
188 CHAPTER 23 CLICK 301Physical Featurese Click 301 has several communication ports, as well as features for conguration (see Figure 23.2).Fig
18 CHAPTER 2 T-BUS BASICSAdding a T-bus to the DIN RailPlacing the T-bus on the DIN rail is quick and easy. To attach a T-bus connector to the ra
CHAPTER 23 CLICK 301 189Configuration Featurese faceplate of the Click 301 has three activity indicator LEDs: PWR (red) lights up when the de
190 CHAPTER 23 CLICK 301NoteOn certain devices, the yellow LED may replace the green LED in the autobaud pro-cess—that is, the yellow LED will co
CHAPTER 23 CLICK 301 191applications. Use the list below to nd the appropriate driver for your application. If you intend to connect from yo
192 CHAPTER 23 CLICK 301e following settings are common to both application drivers.Setting DescriptionDescriptionShows a description of the dev
CHAPTER 23 CLICK 301 193Figure 23.5 – About Tabe following settings are common to both application drivers:Settings DescriptionDriverNames the
194 CHAPTER 23 CLICK 301Figure 23.6 – Diagnostics TabOnce you have nished, use the menu bar at the top of the screen to save your settings, retu
CHAPTER 23 CLICK 301 195e System > General tab combines elements of the Setup and About tabs from the other drivers (see Figure 23.7 and Ta
196 CHAPTER 23 CLICK 301Figure 23.8 – Expert Driver Comm TabSetting DescriptionBaud RateAllows you to change the baud rate at which the device co
CHAPTER 23 CLICK 301 197 Figure 23.9 – Expert Driver Autobaud TabSetting DescriptionCommandAllows you to set the command sent from the device d
198 CHAPTER 23 CLICK 301Figure 23.10 – Expert Driver Network TabSetting DescriptionLocal IPLets you view and change the IP address currently assi
Click 100–400 SeriesUSER GUIDEwww.wavetronix.com 78 East 1700 South Provo, Utah 84606 801.734.7200
CHAPTER 2 T-BUS BASICS 19Figure 2.1 – Wiring Power into the Click 200Wiring through a 5-screw TerminalIf you choose not to use a Click 200, or
CHAPTER 23 CLICK 301 199Figure 23.11 – Expert Driver Server TabSetting DescriptionTelnet PasswordAllows you to enter the password required for
200 CHAPTER 23 CLICK 301Figure 23.12 – Expert Driver Connect Tab Setting DescriptionIncoming Connec-tionAllows you to configure how the device rea
CHAPTER 23 CLICK 301 201StartupAllows you to configure active startup settings.No Activity, the default, does not attempt to initiate a connecti
202 CHAPTER 23 CLICK 301Figure 23.13 – Expert Driver Disconnect TabSetting DescriptionDisconnect ModeAllows you to set conditions under which the
CHAPTER 23 CLICK 301 203Figure 23.14 – Expert Driver Packing TabSetting DescriptionPacking AlgorithmEnables packing, which defines how long the
204 CHAPTER 23 CLICK 301e host list supports a minimum of 1 and a maximum of 12 entries. Each entry contains an IP address and a port number. e
CHAPTER 23 CLICK 301 205If a problem is detected, the program will display a red square next to the item in question. If no problems are detect
In this chapter Physical Features On-device Configuration Computer Configuration24e Click 304 converts half-duplex RS-232 communication to RS-485
208 CHAPTER 24 CLICK 304Physical Featurese Click 304 has several communication ports, as well as features for conguration.Figure 24.2 – Diagram
20 CHAPTER 2 T-BUS BASICSWiring out of a T-busOccasionally you will need to provide power and communication to devices in your cabinet that are n
CHAPTER 24 CLICK 304 209Configuration Featurese faceplate of the Click 304 has the following three LEDs: PWR (red) lights up when the device
210 CHAPTER 24 CLICK 304NoteOn certain devices, the yellow LED may replace the green LED in the autobaud pro-cess—that is, the yellow LED will co
CHAPTER 24 CLICK 304 211eld for the Click 304, should only be used under the direction of Wavetronix Technical Services.Aer you have made con
212 CHAPTER 24 CLICK 304Device IDGives the ID number of the device being configured, which is used to identify the device when you are connecting
CHAPTER 24 CLICK 304 213Figure 24.6 – SmartSensor Driver Diagnostics TabOnce you have nished, use the menu bar at the top of the screen to sav
214 CHAPTER 24 CLICK 304the SmartSensor driver and those available only through this driver. e driver is divided into two tabs—System and Diagno
CHAPTER 24 CLICK 304 21524.8 and Table 24.5).Figure 24.8 – Expert Driver Comm TabSetting DescriptionBaud RateAllows you to change the baud rate
216 CHAPTER 24 CLICK 304Figure 24.9 – Expert Driver Autobaud TabSetting DescriptionCommandAllows you to set the command sent from the device duri
CHAPTER 24 CLICK 304 217Figure 24.10 – Expert Driver Diagnostics TabOnce you have nished, use the menu bar at the top of the screen to save yo
In this chapter Working with Screw Terminal Blocks RS-485 Communication RS-232 Communication3You are now ready to begin adding Click modules to
In this chapter Physical Features Installation Switching Characteristics25e Click 330/331 are used for quick and cost-eective Ethernet network
220 CHAPTER 26 CLICK 330/331Physical FeaturesClick 330/331 modules have several Ethernet ports, allowing you to create a quick Ethernet network b
CHAPTER 26 CLICK 330/331 221Status MeaningOn Supply voltage is in an acceptable rangeO Supply voltage is too lowTable 25.1 – Power Monitor LED
222 CHAPTER 26 CLICK 330/331Follow the steps below to install and wire a Click 330/331:1 Attach the device to a location on the DIN rail that is
CHAPTER 26 CLICK 330/331 223Quality of Service (QoS): IEEE 802.1P/Qe SFN switches are capable of reading Ethernet packets that have already be
In this chapter Physical Features Installation26e Click 340/341/342 are managed Ethernet switches that work with trac monitoring devices. ese s
226 CHAPTER 27 CLICK 340/341/342Physical FeaturesEach Click 340/341/342 module has several communication options, as well as features for monitor
CHAPTER 27 CLICK 340/341/342 227 US1 – Supply voltage for +US1 GND – Ground for US1 US2 – Supply voltage for +US2 GND – Ground for US2
228 CHAPTER 27 CLICK 340/341/342meaning that power and communications will have to be wired in. Follow the steps below to install and wire a Clic
22 CHAPTER 3 WIRING THE DEVICESFigure 3.1 – Removing and Wiring Screw Terminal BlocksRS-485 CommunicationAnother feature that is common to many C
In this chapter Physical Features On-device Configuration Computer Configuration27e Click 400 is a 900 MHz spread spectrum radio with two RS-485
230 CHAPTER 28 CLICK 400Physical Featurese Click 400 has several communication ports, as well as features for conguration.Figure 27.2 – Diagram
CHAPTER 28 CLICK 400 231Configuration Featurese faceplate of the Click 400 has the following four LEDs: PWR (red) lights up when the device
232 CHAPTER 28 CLICK 400Autobaud (solid green)e Autobaud mode is used to match baud rates with an external device. By default, the device will a
CHAPTER 28 CLICK 400 233ashing. e red LED should be solid and the green and yellow LEDs will ash. Wait for a few seconds and the device will
234 CHAPTER 28 CLICK 400onto the device.NoteSome settings appear on multiple drivers. Changing one of those settings on any driver and saving the
CHAPTER 28 CLICK 400 235Device IDGives the ID number of the device being configured, which is used to identify the device when you are connectin
236 CHAPTER 28 CLICK 400Firmware VersionShows the version of firmware your device currently has installed. If Click Supervisor detects a discrepan
CHAPTER 28 CLICK 400 237NoteIf you do not save your settings to your Click 400, they will be lost the next time you power the device down. e
238 CHAPTER 28 CLICK 400DescriptionShows a description of the device being configured. This is only for your information and does not aect the op
CHAPTER 3 WIRING THE DEVICES 23NoteIf you are using a Click 200 in your installation, it is recommended you wire RS-485 through it if you would
CHAPTER 28 CLICK 400 239Data BitsShows you the number of data bits being sent. This option currently cannot be changed.Active PortIndicates on
240 CHAPTER 28 CLICK 400Figure 27.10 – Expert Driver Config 1 TabSetting DescriptionRF ChannelSpecifies the frequency channel of the device (the ch
CHAPTER 28 CLICK 400 241Figure 27.11 – Expert Driver Config 2 TabSetting DescriptionCTS AssertedReserved for hardware handshaking. This field is
242 CHAPTER 28 CLICK 400Setting DescriptionRF Packet SizeAllows you to set the maximum size of an RF packet before it is sent.Interface TimeoutAl
CHAPTER 28 CLICK 400 243NoteIf you do not save your settings to your Click 400, they will be lost the next time you power the device down. e
In this chapter Physical Features On-device Configuration Computer Configuration28e Click 421 serial to Bluetooth radio converts half-duplex two-
246 CHAPTER 29 CLICK 421Physical Featurese Click 421 has several communication ports, plus features for conguration.Figure 28.2 – Diagram of th
CHAPTER 29 CLICK 421 247mounted on the exterior of the trac cabinet or up on a pole for maximum range. A whip antenna can also be used inside
248 CHAPTER 29 CLICK 421module will attempt to match baud rates with a SmartSensor on the bus; however, the de-vice can be congured to autobaud
24 CHAPTER 3 WIRING THE DEVICESRS-232 CommunicationMost Click devices also feature RS-232 communication capabilities. ese modules will convert t
CHAPTER 29 CLICK 421 249Computer Configuratione Click 421 can be congured more exactly using the Click Supervisor soware. See Chapters 4 and
250 CHAPTER 29 CLICK 421SmartSensor DriverWhen you open the SmartSensor driver, you will see three tabs: Setup, About and Diag-nostics.Under the
CHAPTER 29 CLICK 421 251Figure 28.5 – SmartSensor Driver About TabSetting DescriptionDriverNames the driver you are currently working with.Seri
252 CHAPTER 29 CLICK 421Figure 28.6 – SmartSensor Driver Diagnostics TabOnce you have nished, use the menu bar at the top of the screen to save
CHAPTER 29 CLICK 421 253e System tab is divided into three subtabs: General, Comm, and Autobaud.e General subtab contains information about t
254 CHAPTER 29 CLICK 421Figure 28.8 – Expert Driver Comm TabSetting DescriptionBaud RateAllows you to change the baud rate at which the device co
CHAPTER 29 CLICK 421 255Figure 28.9 – Expert Driver Autobaud TabSetting DescriptionCommandAllows you to set the command sent from the device du
256 CHAPTER 29 CLICK 421Figure 28.10 – Expert Driver Bluetooth TabSetting DescriptionBluetooth NameAllows you to change the name of your Bluetoot
CHAPTER 29 CLICK 421 257Figure 28.11 – Expert Driver Diagnostics TabOnce you have nished, use the menu bar at the top of the screen to save yo
CHAPTER 3 WIRING THE DEVICES 25Figure 3.4 – Wiring RS-232 Communication into the Click 200Wiring RS-232 from a Click DeviceMany Click modules f
www.wavetronix.com
In this chapter Installing Click Supervisor Microsoft .NET Framework4Once your Click devices are installed and wired, the next step is to install
28 CHAPTER 4 INSTALLING CLICK SUPERVISORNoteIf you are running Windows® Vista, you must run Click Supervisor in XP Service Pack 2 compatibility m
© 2014 Wavetronix LLC. All Rights Reserved.Wavetronix, SmartSensor, Click, Command, and all associated product names and logos are trademarks of Wavet
CHAPTER 4 INSTALLING CLICK SUPERVISOR 29To install Click Supervisor on a handheld computer, you need to have ActiveSync (on Win-dows XP or earl
30 CHAPTER 4 INSTALLING CLICK SUPERVISORFigure 4.3 – Location to Be Installed3 Click the Install Now button.4 Aer Click Supervisor is installe
CHAPTER 4 INSTALLING CLICK SUPERVISOR 31Use these steps to install Click Supervisor on a handheld computer:1 Ensure that you have ActiveSync o
32 CHAPTER 4 INSTALLING CLICK SUPERVISORFigure 4.6 – Microsoft .NET Framework PromptUse the following steps to install Microso .NET Framework:1
Using Click Supervisor 5 In this chapter Connecting to Your Computer Accessing the Communication Screen Serial Communication IP Communication
34 CHAPTER 5 USING CLICK SUPERVISORConnecting the computer to another device that has a RS-232 port but is not computer-programmable, such as the
CHAPTER 5 USING CLICK SUPERVISOR 35Serial Communicatione rst section on the Communication screen is Serial Communication. Here you can connec
36 CHAPTER 5 USING CLICK SUPERVISORConnecting to a DeviceClick Supervisor can talk to one device at a time. ere are two ways to select which mod
CHAPTER 5 USING CLICK SUPERVISOR 373 Click on the device you’d like to connect to and hit Select. Aer downloading the com-munication le, the
38 CHAPTER 5 USING CLICK SUPERVISORAlternatively, you can connect without the ID number:1 Leave a 0 in the Click ID text eld. Click Supervisor
ContentsIntroduction 7Using this Manual 7Part I Introduction to the Click SeriesChapter 1 The Power Plant 11Connecting to a Circuit Breaker 12 • Co
CHAPTER 5 USING CLICK SUPERVISOR 39To open a backup, select the Backups radio button in the lower righthand corner of the screen. All the backu
Part IIIndividual Click 100–400 Series ModulesChapter 6 – Click 100Chapter 7 – Click 101Chapter 8 – Click 104Chapter 9 – Click 110Chapter 10 – Click 1
In this chapter Physical Features On-device Configuration Troubleshooting6e Click 100 is a hot-swappable contact closure module for use with the
44 CHAPTER 6 CLICK 100Physical Featurese Click 100 has eight primary and eight secondary contact outputs, which all share a logic ground (see Fi
CHAPTER 6 CLICK 100 45Primary DetectorSecondary DetectorTraffic DirectionFigure 6.3 – Primary and Secondary OutputsFigure 6.4 below shows a dia
46 CHAPTER 6 CLICK 100 AC (Actuation) – Green 1L (One Loop Speed) – Yel lowe front also has a push-button labeled Mode Switch, which is used
CHAPTER 6 CLICK 100 47Operation ModesPress and hold the push-button to cycle through the dierent operation modes; release the button when the
48 CHAPTER 6 CLICK 1001L (One Loop Speed) Yellow Outputs contact closures for single-loop emulation. The duration of each contact closure output
Chapter 6 Click 100 — 16 Output Contact Closure 43Physical Features 44 • Troubleshooting 48Chapter 7 Click 101 — Multi-sensor to Contact Closure 4
In this chapter Physical Features Installation On-device Configuration Computer Configuration7e Click 101 is a contact closure module that is
50 CHAPTER 7 CLICK 101Each side-re sensor can use its two communication ports to send real-time trac data to both cabinets for which it is coll
CHAPTER 7 CLICK 101 51Sensor ID 2112345Sensor ID 20Click! 101Cabinet A12345ф2ф6Figure 7.3 – The Click 101 Collects from Multiple SensorsMore se
52 CHAPTER 7 CLICK 101Figure 7.4 – Diagram of the Click 101Communication Portse back of the Click 101 features a 5-position connector that plugs
CHAPTER 7 CLICK 101 53NoteAfter you have completed programming the device using Click Supervisor, remove the RS-232 serial cable from the DB-9
54 CHAPTER 7 CLICK 101e screw terminals labeled C1–C4 represent the common lines for each contact closure output pluggable screw terminal block
CHAPTER 7 CLICK 101 55NoteYou will only be able to communicate properly if the Click 101 and each sensor’s RS-485 baud rate match.To reset the
56 CHAPTER 7 CLICK 101Figure 7.5 – Expert Driver General TabSetting DescriptionModuleAllows you to enter a name and description of the device. Dr
CHAPTER 7 CLICK 101 57Figure 7.6 – Expert Driver Comm TabSetting DescriptionBaud RateAllows you to change the baud rate for both the RS-485 and
58 CHAPTER 7 CLICK 101Figure 7.7 – Expert Driver Autobaud TabSetting DescriptionCommandAllows you to set the command sent from the device during
Chapter 16 Click 210 — AC Circuit Breaker 161Physical Features 162 • Installation 162Chapter 17 Click 211 — AC Outlet 163Physical Features 164 • I
CHAPTER 7 CLICK 101 59Setting DescriptionSensor IDThe sensor’s multi-drop communication ID.Contact Closure OutputsAllows you to set the Click 1
60 CHAPTER 7 CLICK 101Under the Diagnostics tab, you can run diagnostics on your device (see Figure 7.10). Click the General button to run diagno
In this chapter Physical Features Installation Configuration Rotary Switch Front Panel Menu Click Supervisor8e Click 104 is a 4-channel co
62 CHAPTER 4 CLICK 104Physical Featurese Click 104 has the following physical features.T-BusConnectorRS-232 ConnectorOutputs 1-2 ConnectorMode S
CHAPTER 4 CLICK 104 63pre-wire the Click 104 before nal installation. Rotary SwitchOn the faceplate of the device is a rotary switch, numbered
64 CHAPTER 4 CLICK 104bus 1 (data) or bus 2 (control). Level 2 LEDs display conguration options for the menu items selected via the level 1 LEDs
CHAPTER 4 CLICK 104 65change the amount of time that must elapse without the device receiving a pertinent data-gram before the device enters fa
66 CHAPTER 4 CLICK 104able to congure all other parameters (besides channel input mapping) using the front panel menu and Click Supervisor.NoteI
CHAPTER 4 CLICK 104 679 33–36Table 8.2 – Click 104 Rotary Switch Channel Input Map SettingsTo set the switch, insert a small screwdriver into t
68 CHAPTER 4 CLICK 104light up to indicate that the device is cycling through all menu options (specics on these menu options, and which LEDs an
Physical Features 230 • On-device Conguration 231 • Com-puter Conguration 233Chapter 28 Click 421 — Serial to Bluetooth® Radio 245Physical Feature
CHAPTER 4 CLICK 104 69Press and release Configuration parameter selected; autobaud commences (will show intermediate LED states); auto-baud finis
70 CHAPTER 4 CLICK 104NoteThis parameter can also be changed using the rotary switch or Click Supervisor. As mentioned earlier, the Click 104 dev
CHAPTER 4 CLICK 104 71Autobaude second option that comes up when you’re cycling through the front panel menu is the autobaud function. To sele
72 CHAPTER 4 CLICK 104NoteThis parameter can also be changed using Click Supervisor. Level 1 LEDs Baud rate for bus 1 Baud rat
CHAPTER 4 CLICK 104 73See the earlier Navigating through the Menu and the Menu Operation Example sections for how to view this parameter.Aer t
74 CHAPTER 4 CLICK 104e Backups option can be used to read congurations that have previously been saved to le. See Chapter 5 for more informat
CHAPTER 4 CLICK 104 75Firmware VersionShows the version of firmware your device currently has installed. If Click Supervisor detects a discrepan
76 CHAPTER 4 CLICK 104Input MappingLets you assign input datagram channels received from the sensor to the two or four output channels on the dev
CHAPTER 4 CLICK 104 77NoteIf you do not save your settings to your Click 104, they will be lost the next time you power the device down. e
In the introduction Using this ManualWavetronix Click products are a simple and cost-eective way to connect various trac components into a single,
In this chapter Physical Features Installation and Wiring Operation Configuration9e Click 110 is used to report vehicle data to a MIDAS outsta
80 CHAPTER 9 CLICK 110Physical Featurese following sections describe the physical features of the Click 110 card.Figure 9.2 – Diagram of the Cli
CHAPTER 9 CLICK 110 81Detection 1 2 3 4Fault Menu PWR MF TD RD 1 2 3 4Figure 9.3 – Click 110 LEDse detection in
82 CHAPTER 9 CLICK 110Push-buttonse faceplate of the Click 110 features two push-buttons. e upper push-button, labeled Mode Switch, is used to
CHAPTER 9 CLICK 110 83A1Pin DescriptionA1 Channel 1, normally closedA2 No connectionA3 Channel 1, normally openA4 No connectionA5 No connection
84 CHAPTER 9 CLICK 110A1Pin DescriptionA1 Channel 1, normally closedA2 No connectionA3 Channel 1, normally openA4 No connectionA5 No connectionA6
CHAPTER 9 CLICK 110 85Preparing the SmartSensorIn addition to wiring the SmartSensor to the Click 110, you must also make sure that the SmartSe
86 CHAPTER 9 CLICK 110Location No No YesDevice ID No No YesFault Status No Fault Indicators Read-onlyTo use this configuration feature:Hardware C
CHAPTER 9 CLICK 110 87Figure 9.6 – Click 110 DIP Switchese Click 110 features three DIP switches labeled S1, S2 and S3 on the label and in the
88 CHAPTER 9 CLICK 110NoteThis parameter can also be changed using the front panel menu or Click Supervisor.e switch patterns for the two parame
8 INTRODUCTION CLICK 100–400 SERIES USER GUIDEClick Supervisor soware, which is used with certain Click devices for conguration. For a list of
CHAPTER 9 CLICK 110 89A disabled output will never enter the detection state, and will never indicate a fault condi-tion. Any combination of ou
90 CHAPTER 9 CLICK 110NoteThis parameter can also be changed using the front panel menu or Click Supervisor.As mentioned earlier, the Click 110 d
CHAPTER 9 CLICK 110 91Outstation ModeAlso on this switch is the outstation mode. is is congured on the third DIP switch, la-beled S3, using s
92 CHAPTER 9 CLICK 110Fault latching involves how the Click 110 reacts when the ow of data from the connected SmartSensor is interrupted. As men
CHAPTER 9 CLICK 110 93Level 1Mode SwitchLevel 2 Menu PWR MF TD RD 1 2 3 4Figure 9.7 – Menu Indicator LEDs and Mode SwitchNoteThe
94 CHAPTER 9 CLICK 110Mode Switch Action Display StateNone Normal operationPress and hold Channel map menu option displayedContinue holding Autob
CHAPTER 9 CLICK 110 95Level 1 LEDsAutobaud SettingsPerform Autobaud on Bus 1Perform Autobaud on Bus 2Cancel and Exit MenuLevel 2 LEDsLevel 1 LE
96 CHAPTER 9 CLICK 110NoteThis parameter can also be changed using the DIP switches or Click Supervisor. As mentioned earlier, the Click 110 devi
CHAPTER 9 CLICK 110 97Autobaude second option that comes up when you’re cycling through the front panel menu is the autobaud function. is opt
98 CHAPTER 9 CLICK 110Baud Rate (Bus 1 and 2)e next two conguration parameters that come up in the front panel menu allow you to manually set t
Comments to this Manuals